Logged in as

Customer Service

Available jobs

Job opportunities at Elvaco

Elvaco is a growing company with talented, down-to-earth people who want to deliver that little extra while at the same time having fun!

 

Apply now!

CMeX50

1050062

CMeX50 - Wireless M-Bus Receiver (868MHz)

CMeX50 collects data via wireless M-Bus on the 868MHz frequency band. Wireless M-Bus antenna is not included and must be purchased seperately.

Mechanics

Casing material:
Polyamide
Dimensions (w x h x d):
105 x 90 x 65 mm (6 DIN modules)
Protection class:
IP20
Weight:
220 g
Mounting:
Mounted on DIN rail (DIN 50022) 35 mm

Electrical connections

Supply voltage:
Screw terminal. Cable 0.5-2.5 mm², 0.5 Nm tightening torque
M-Bus master port:
Screw terminal cable 0.5-2.5 mm², 0.5 Nm tightening torque
M-Bus slave port:
Pin terminal solid wire 0.6-0.8 Ø mm
RS232:
RJ45 8/8
USB slave port:
Type mini B

Electrical characteristics

Nominal voltage:
100-240 VAC (±10%)
Frequency:
50/60 Hz
Power consumption (nom):
<6 W
Installation category:
CAT 2
Unit loads:
1T/1.5 mA

Environmental specifications

Operating temperature:
-30 °C to +55 °C (reduced response time on LCD at low temperatures)
Operating humidity:
5 % to 90 %, non-condensing
Operating altitude:
0-2000 m
Pollution degree:
Degree 2
Usage environment:
Indoors, can be extended with IP67 enclosure for outdoor use
Storage temperature:
-40 °C to +85 °C

Temperature sensor, margin of error

Humidity sensor, margin of error

User interface

LCD diplay:
Graphic monochrome
Display resolution:
128 x 64 pixels
Keyboard:
7 illuminated buttons

M-Bus

Interfaces:
IR, integrated M-Bus Master, Wireless M-Bus Receiver, M-Bus slave
M-Bus standard:
EN 13757 and EN 13757-4
Decryption:
Yes

Wireless M-Bus

Integrated M-Bus Master

Nominal voltage, master port:
28 VDC
M-Bus baud rate, master port:
300 and 2400 bit/s
M-Bus search modes:
Primary, secondary
Maximum cable length:
1000 m (100 nF/km, maximum 90 ohm)
Maximum number of unit loads (hardware limit):
32T/48 mA

Wireless M-Bus Receiver

Modes:
S1, T1, C1
Maximum number of Wireless M-Bus devices:
800
Radio frequency band:
868 MHz
Encryption, Wireless M-Bus:
AES-128
RF sensitivity:
-105 dBm
OMS compliant:
Yes

M-Bus slave interface

M-Bus baud rate, slave port:
300 and 2400 bit/s
Nominal voltage, slave port:
21-42 VDC
Addressing modes:
Primary, secondary
Default address:
251

General

Data storage (examples)

Mobile Network

Fixed Network (Ethernet)

Integration

Approvals

EMC:
EN 61000-6-2, EN 61000-6-3
Safety:
EN 61010-1

Connections and Interfaces

Transmissions